Numeric sensor Inlet Temp going high (upper non-recoverable) has asserted.
has asserted.
Explanation
The inlet temperature has exceeded its specified threshold.
The compute node has initiated a hard shutdown.
May also be shown as
80010b013701ffff or 0x80010b013701ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
CIM Information
Prefix: PLAT and ID:
0498
SNMP Trap ID
0
Automatically notify Support
No
User response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module or Flex System Manager event log
for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the chassis is not
obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.