Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted.
Explanation
The inlet temperature has exceeded its specified threshold. The compute node has attempted a soft shutdown.
May also be shown as
800109013702ffff or 0x800109013702ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
CIM Information
Prefix: PLAT and ID:
0494
SNMP Trap ID
0
Automatically notify Support
No
User response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module or Flex System Manager event log
for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the chassis is not
obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.