(Trained service technician only) Use these instructions
to install a fan distribution card in the Flex System Enterprise
Chassis.
To install the fan distribution card, complete the following
steps.
- Insert the fan distribution card into the slot on the shuttle.
- Align the pin holes on the fan distribution card with the
alignment pins on the shuttle, align the 80 mm fan module connectors
with the openings in the safety mesh on the chassis, and slide the
fan distribution card down to lock it in place.
Note: Be
sure to hold the card evenly on the top and bottom. When everything
is aligned correctly, the fan module connectors will suddenly go through
the openings in the mesh, and the alignment pins will go through the
pin holes on the fan distribution card.
- Tighten the thumbscrew that you removed earlier to secure
the fan distribution card to the shuttle.
- Connect the 40 mm fan module cable to the connector on
the fan distribution card.
- Connect the fan logic module cable to the fan distribution
card. Make sure that both of the bail latches are in the locked position
to secure the cable.
- Install the fan distribution card power cable connector
into the shuttle:
- Insert the left side of the power cable connector through
the slot at the bottom of the shuttle.
- Push the power connector to the right far enough so
that the key tab aligns with the notch in the slot; then, slide the
connector to the left until it snaps into place.
- Route the fan distribution card power cable through
the cable-management clip and lock the clip to the secure the cable.
After you install the fan distribution card, complete the
following steps:
- Reinstall the chassis shuttle into the chassis (see Replacing the shuttle).
- Reinstall the components that you removed from the rear of the
chassis.
- Connect any cables that you disconnected from the modules in the
rear of the chassis.
- Connect the chassis to power (see Connecting the chassis to power).
- Restart any compute nodes that
you shut down. See the documentation that comes with each compute node for
detailed instructions.
- Restart the management node, if one is installed. See the Flex System Manager Installation
and Service Guide for instructions.