Chassis ambient temperature is out of range.
The ambient temperature of the chassis is outside of the operational range.
Alert Category
Chassis/System Management (Warning)
Chassis LED that is Lit
Chassis Check Log
CIM Information
Prefix:CMM
and ID:0823
SNMP Trap ID
mmTrapChassisN
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the ambient room temperature to ensure that the room is not too hot.
- Check for any blockage on or near the ventilation holes on the chassis.
Remove any blockages that you find.
- Make sure that a device or filler is installed in each bay
in the front and rear of the chassis,
and make sure that nothing is covering the bays.
Empty bays can cause a reduction in airflow to the devices in the chassis.
- Make sure that enough fan modules are installed to sufficiently cool
the devices in the chassis.
See the chassis documentation to determine
how many fan modules are required.