80010701-3701ffff
Numeric sensor [NumericSensorElementName] going high (upper non-critical) has asserted.

Explanation

The inlet 1 temperature has exceeded its specified threshold. The compute node has attempted a soft shutdown.

May also be shown as 800107013701ffff or 0x800107013701ffff

Severity

Warning

Alert Category

Warning - Temperature

Serviceable

Yes

CIM Information

Prefix: PLAT and ID: 0490

SNMP Trap ID

12

Automatically notify Support

No

User response

Complete the following steps until the problem is solved:
  1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
  2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
  3. Make sure that the room temperature is within operating specifications.