You can install up to seven 2-bay compute nodes in
the chassis. A 2-bay device occupies two adjacent node bays (horizontally)
in the chassis.
Before you install a
compute node in
the
Flex System Carrier-Grade
chassis,
complete the following steps:
- Verify that the compute node is
compatible with the chassis. See the Lenovo ServerProven website.
- Make sure that enough power supplies and fan modules are installed
in the chassis to support the compute node. See Installing components to
determine the number of power supplies and 80 mm fan modules that
are required and where they should be installed in your chassis configuration.
- Read the instructions that come with the compute node.
- Make sure that you have installed any optional hardware devices
in the compute node.
- Select the bays for the compute node. Two
adjacent bays are required.
To install a 2-bay compute node, complete
the following steps:
- Remove the airborne contaminant filter assembly bezel,
if one is installed (see Removing the airborne contaminant filter assembly).
Note: Remove only the airborne contaminant filter assembly bezel.
You do not need to remove the filter assembly mounting brackets in
order to install a compute node.
- Remove the node bay fillers, if they are installed. Push
the filler release tab to the right; then, grasp the filler by the
slot and pull it out of the bay.
- Remove the chassis shelf, if one is installed (see Removing a chassis shelf).
- Open both release handles (rotate the left handle to the
left and rotate the right handle to the right).
- Slide the compute node into
the node bays until it is seated.
- Close both release handles.
After you install the
compute node, complete
the following steps:
- Make a note of the compute node identification
information on one of the labels that come with the Flex System Carrier-Grade
chassis.
Place a label on the node label tab. See User labels for more information.
Important: Do
not place the label on the compute node or
in any way block the ventilation holes on the chassis.
- Install the airborne contaminant filter assembly bezel (see Replacing the airborne contaminant filter assembly).